NEC 404.9(B) · Homes and commercial

Grounding switches and metal cover plates

Light switches, dimmers and control switches must connect to an equipment grounding conductor and allow a metal faceplate to be bonded. Where a switch box has no ground, a narrow exception applies to replacement switches.

What the code requires

Snap switches, dimmers and control switches must be connected to an equipment grounding conductor. They must provide a way to bond a metal faceplate, whether or not a metal plate is installed, and any metal faceplate must be bonded.

Two methods are allowed. Metal mounting screws can connect the switch to a grounded metal box or cover, or to a nonmetallic box with a built-in grounding means. Or an equipment grounding conductor or bonding jumper can be connected to the switch's grounding terminal.

On the job

  • In older homes without a ground wire, metal plates on new switches without GFCI protection are a common correction.
  • Smart switches with the green grounding lead left unconnected are another frequent problem.
Single toggle light switch with a white cover plate on a white wall
Light switch on a wall (representative stock photo).

Exceptions that matter

  • Replacement only, with no ground in the box: a switch within 8 ft (2.5 m) vertically or 5 ft (1.5 m) horizontally of ground or grounded metal needs a nonconducting, noncombustible faceplate with nonmetallic screws, unless the yoke is nonmetallic or the circuit is GFCI-protected.
  • Listed kits that meet specific nonmetallic conditions.
  • Snap switches with integral nonmetallic enclosures under 300.15(E).