NEC 702.5 · Homes

Transfer switches and interlocks for standby power

An optional standby system needs listed transfer or interconnection equipment that prevents the standby source and the normal supply from being connected by accident. The listing requirement is not new in 2023; it was relocated within the section.

What the code requires

Section 702.5 requires interconnection or transfer equipment for every optional standby system, such as a home generator. The equipment must suit its use, must be listed, and must be designed and installed so that the standby source and the normal supply cannot be connected to each other by accident.

Some transfer switches install between the utility meter and the meter enclosure. Under 702.5(B), these must be listed meter-mounted transfer switches and must be approved. An informational note points to UL 1008M, the standard for these switches, and another explains that manual and nonautomatic equipment relies on a person to operate it.

Except in dwelling units, 702.5(C) requires the equipment's short-circuit current rating to be field-marked on its exterior, based on the type and settings of the overcurrent device that protects it. If the standby system can run in parallel with the normal source, 702.5(D) also requires it to meet Article 705, Part I or Part II.

On the job

  • Transfer equipment must be listed, such as a listed transfer switch or a listed interlock kit. Backfeeding a panel from a generator through an unlisted setup does not meet the code.
  • A transfer switch mounted at the meter must be the listed meter-mounted type and must be approved by your inspector.
  • Outside of dwelling units, look for the field-marked short-circuit current rating on the outside of the transfer equipment.
Black and white photo of an open-frame portable generator
Portable generator (representative stock photo).

Exceptions that matter

  • A portable generator may be connected temporarily without transfer equipment only where qualified persons service the installation and the normal supply is isolated by a lockable disconnect or by disconnecting the normal-supply conductors.

What changed in 2023

The 2023 NEC added interconnection equipment to the title, dropped the 2020 limit to systems where the utility is the normal or standby source, moved the existing listing requirement into 702.5(A) rather than adding a new one, and dropped the 2020 rule that meter-mounted transfer switches be the manual type unless rated for automatic loads.