NEC 440.3 · Homes · California rule

California: heat-pump-ready circuit at gas furnaces

In a new California one- or two-family home with a gas or propane furnace, the 2025 Energy Code requires a 240-volt, 30-amp-minimum circuit within 3 ft of the furnace and a reserved, marked double-pole breaker space for a future heat pump.

What the code requires

The 2025 California Electrical Code adds section 440.3, which points to California Energy Code §150.0(t). It applies to each dwelling unit in new buildings with one or two dwellings when a gas or propane furnace serves the home. Other gas equipment does not trigger it.

The home needs a dedicated 240-volt branch circuit within 3 ft of the furnace, accessible with no obstructions, with conductors rated 30 A minimum. It ends at a blank cover identified as 240V ready. The main service panel needs a reserved double-pole breaker space permanently marked For Future 240V use.

No receptacle or breaker has to be installed at construction, and the circuit may not serve other appliances. All components must meet the California Electrical Code.

On the job

  • A cover without the 240V ready identification, or a panel space without the For Future 240V use marking, does not comply.
  • A circuit that ends more than 3 ft from the furnace does not comply.
  • The reserved space takes up a breaker position in the main panel; see 408.2 for how the reserved spaces add up in a new home.
Outdoor heat pump unit mounted beside a house with lap siding
Outdoor heat pump unit (representative stock photo).

Exceptions that matter

  • Applies only to newly constructed buildings. Additions and alterations are not covered.
  • Not required when electric or heat pump space heating is installed.
  • Applies to permit applications filed on or after Jan 1, 2026.

In California

For multifamily buildings, the 2025 Energy Code places the same 240-volt, 30-amp, 3 ft rule in §160.9(b), while the CEC text still cites an older subsection letter, so confirm with your building department.