NEC 430.32 · Commercial

Overload protection for motors

A continuous-duty motor over 1 hp needs overload protection, usually a separate overload device sized from its nameplate current: generally no more than 125% with a service factor of 1.15 or more or a temperature rise of 40 °C or less, 115% for others.

What the code requires

A continuous-duty motor rated more than 1 hp must be protected against overload in one of four ways: a separate overload device; an approved thermal protector built into the motor, or approved electronic protection; a protective device built into a motor that is part of an approved assembly that does not normally overload it; or, above 1500 hp, embedded temperature detectors. A separate device is generally selected at no more than 125% of the motor's nameplate current when the motor has a marked service factor of 1.15 or more, or a marked temperature rise of 40 °C or less. For all other motors, the limit is generally 115%.

Overload devices are sized from the current on the motor's nameplate, not from table full-load current values.

For a motor of 1 hp or less that is manually started, not permanently installed, and within sight of its controller, the branch-circuit short-circuit and ground-fault protective device may also provide overload protection. That device can be no larger than Part IV of Article 430 allows.

On the job

  • Overloads set from table full-load current instead of the motor nameplate are a common error.
  • Separate from 430.32, NFPA TIA 23-20 (effective Sept 9, 2025) adds 430.132, which prohibits GFCI or SPGFCI protection between power-conversion equipment and motors. California may print the code without later TIAs, so confirm with your building department.
Blue industrial electric motor among stainless steel process piping
Industrial electric motor (representative stock photo).

Exceptions that matter

  • A small motor meeting the conditions above is acceptable on a 120-volt circuit protected at not over 20 A.
  • If the small motor is not within sight of its controller, overload protection must follow 430.32(B) instead.

Related sections

  • NEC 430.6(A)(2)
  • NEC 430.52
  • NEC 430.55
  • NEC 240.6(A)
  • NEC 430.132