NEC 334.10 · Homes and commercial

Where NM cable (Romex) is allowed

NM cable, often called Romex, is allowed in one- and two-family homes and their garages. In other buildings, it depends on construction type: Types III, IV and V allow it with limits, and Types I and II only inside raceways.

What the code requires

Except where 334.12 prohibits it, NM and NMC cable may be used in one- and two-family homes, including their attached or detached garages and their storage buildings. It may also be used in multifamily dwellings permitted to be of Types III, IV or V construction and, since 2023, in their detached garages.

In other structures permitted to be of Types III, IV or V construction, NM cable is allowed only when concealed in walls, floors or ceilings that provide a thermal barrier with at least a 15-minute finish rating. It is also allowed in cable trays in those structures if the cable is identified for that use.

In buildings of Types I and II construction, NM cable may be used only inside raceways that are permitted in those building types.

On the job

  • On commercial tenant improvements, NM cable needs a building permitted to be Type III, IV or V construction, concealment behind a 15-minute finish, and a space that 334.12 does not exclude. In Types I and II construction, it must be in a raceway.
  • The construction type should be confirmed from the building plans, not guessed.
Interior of a wood-framed house at the rough-in stage
Wood framing at rough-in (representative stock photo).

What changed in 2023

The 2023 NEC added the detached garages of multifamily buildings to the places NM cable is allowed.

In California

California's 2025 code adds a note, for housing regulated by HCD, that construction Types I through V in this section are as defined in the California Building Code.