NEC 240.87 · Commercial

Arc energy reduction for breakers of 1,200 A and up

Where a breaker's highest continuous trip setting is 1,200 A or more, the code requires one of seven arc energy reduction methods set below the available arcing current, with documentation and testing when first installed.

What the code requires

240.87 applies where a circuit breaker's highest continuous trip setting, whether its rating or the highest it can be adjusted to, is 1,200 A or more.

One of seven methods must be provided and set below the available arcing current: zone-selective interlocking; differential relaying; energy-reducing maintenance switching with a local status indicator; an energy-reducing active arc-flash mitigation system; an instantaneous trip setting below the arcing current; an instantaneous override below the arcing current; or an approved equivalent means. Temporarily adjusting the instantaneous trip setting does not count.

Documentation must show the breaker locations and that the method is set below the available arcing current, and be available to authorized persons. The method must be performance tested on site when first installed, by qualified persons following the manufacturer's instructions, using primary current injection or another approved method. A written record of the test must be available to your inspector.

On the job

  • A 1,200 A main breaker installed with no arc-energy method, documentation or test record is a common correction.
  • Using two to six smaller service disconnects (230.71) can keep each device under 1,200 A.
Closed gray commercial switchgear with a hazardous-voltage danger label on the door
Commercial switchgear with a danger label (representative stock photo).

Related sections

Where this comes from

San Clemente · Dana Point · Laguna Beach

Send a photo. Get a real answer.

Text is fastest. If you smell something burning or see smoke, call 911 first and keep away from the panel.

Kyle Robert Anderson KBC Electric · CSLB #1073066 · C-10 Electrical · Licensed since 2021