NEC 110.26(C)(3) · Commercial

Exit doors and panic hardware for large electrical rooms

Where equipment rated 800 A or more has overcurrent, switching or control devices, personnel doors less than 25 ft from the working space must swing in the direction of egress, open at least 90° and have listed panic or fire exit hardware.

What the code requires

110.26(C)(3) applies where equipment rated 800 A or more contains overcurrent, switching or control devices and a personnel door to the working space is less than 25 ft from the nearest edge of that space. Such a door must swing in the direction of egress, open at least 90°, and have either listed panic hardware or listed fire exit hardware.

The companion rule, 110.26(C)(2), covers large equipment. Equipment rated 1200 A or more and over 6 ft wide needs an entrance to the working space at each end, at least 24 in. wide and 6½ ft high. The same applies to service disconnects grouped under 230.71(B) with a combined rating of 1200 A or more and a combined width over 6 ft.

Under (C)(2), a single entrance is allowed instead if the way out of the working space is unobstructed, or if the required working-space depth is doubled.

On the job

  • In a commercial electrical room with 800 A or larger gear, a standard knob or lever lockset on a door within 25 ft of the working space fails. The door needs listed panic or fire exit hardware and must swing out.
  • Door hardware is an architectural item, so coordinate it with the door and hardware schedule early in design.
Closed gray commercial switchgear with a hazardous-voltage danger label on the door
Commercial switchgear with a danger label (representative stock photo).

What changed in 2023

The 2023 edition added the requirement that these doors open at least 90°; the 2020 text required only that they open in the direction of egress and have listed panic or fire exit hardware.